OD MODEL
4TWR4030N1

ID MODEL
TEM4A0B36S31+TDR

NOM CFM
1000

ARI REF #
211164959

Published Date: 06/03/2025

COOLING PERFORMANCE AT INDOOR DRY BULB TEMPERATURES

< font size="3"> OD AMB
ID WBTOT CAP72757880KW
85
5927.2022.7025.627.2027.202.09
6328.6018.5021.424.2026.102.11
6730.5014.4017.320.1022.002.12
7133.1010.4013.316.2018.102.14
95
5925.6022.0024.825.6025.602.37
6326.8017.7020.723.5025.402.39
6728.7013.7016.619.4021.402.41
7131.109.7012.715.5017.402.43
105
5923.9021.3023.623.9023.902.65
6325.1017.1020.022.8024.702.67
6726.8013.0015.918.7020.702.70
7129.109.1012.014.8016.702.73
115
5922.3020.6022.322.3022.302.93
6323.4016.4019.322.1023.402.96
6725.0012.3015.318.1020.002.99
7127.108.4011.314.1016.103.02

USE THE FOLLOWING FACTORS TO COMPENSATE FOR DIFFERENT AIR FLOW

AIR FLOW RATE, CFM.< /font>CAPACITY MULTIPLIERTOTAL POWER MULTIPLIER
8750.980.99
11251.021.01

ARI RATING FOR COOLING

CFMCAPACITY (A) TESTSEER2EER2
9502840014.3011.70

A.R.I. Standard Capacity Rating Conditions

< font size="1">A.R.I. STANDARD 210/240 RATING CONDITIONS — (A) Cooling 80°F. D.B., 67°F. W.B. air entering indoor coil, 95°F. D.B. air entering outdoor coil. (B) High Temperature Heating 47°F. D.B., 43°F. W.B. air entering outdoor coil, 70°F. D.B. air entering indoor coil. (C) Low Temperature Heating 17°F. D.B. ,15°F. W.B. air entering outdoor coil, 70°F. D.B. air entering indoor coil. (D) Rated indoor airflow for heating is the same as for cooling.

 

 

 

OD MODEL
4TWR4030N1

ID MODEL
TEM4A0B36S31+TDR

NOM CFM
1000

ARI REF #
211164959

Published Date: 06/03/2025

HEATING PERFORMANCE AT INDOOR DRY BULB TEMPERATURE

< tr>
 TOTAL CAPACITY MBH.TOTAL POWER IN KILOWATTS
OD AMB6070758060707580
213.5013.3013.1013.001.992.092.142.19
715.1014.9014.7014.602.002.102.152.20
1216.8016.5016.3016.202.012.112.162.21
1718.4018.1017.9017.702.032.132.182.23
2219.4019.0018.8018.702.032.132.182.23
2720.3020.0019.8019.602.032.132.182.23
3221.3020.9020.7020.502.032.132.182.23
3722.9022.5022.3022.102.042.142.192.24
4225.6025.1024.9024.602.072.172.222.27
4728.2027.7027.5027.202.102.202.262.31
5229.9029.3029.0028.802.112.222.272.32
5731.5030.9030.6030.302.122.232.282.34
6233.2032.5032.2031.902.142.242.302.35
6734.8034.1033.8033.502.152.262.312.36
7236.4035.8035.4035.102.162.272.322.38

USE THE FOLLOWING FACTORS TO COMPENSATE FOR DIFFERENT AIR FLOW

AIR FLOW RATE, CFM.< /font>CAPACITY MULTIPLIERTOTAL POWER MULTIPLIER
8750.990.98
11251.011.03

ARI RATING FOR HEATING

CFMCAPACITY 47COP 47CAPACITY 17COP 17HSPF2
950276003.70180002.507.50

A.R.I. Standard Capacity Rating Conditions

< font size="1">A.R.I. STANDARD 210/240 RATING CONDITIONS — (A) Cooling 80°F. D.B., 67°F. W.B. air entering indoor coil, 95°F. D.B. air entering outdoor coil. (B) High Temperature Heating 47°F. D.B., 43°F. W.B. air entering outdoor coil, 70°F. D.B. air entering indoor coil. (C) Low Temperature Heating 17°F. D.B. ,15°F. W.B. air entering outdoor coil, 70°F. D.B. air entering indoor coil. (D) Rated indoor airflow for heating is the same as for cooling.