OD MODEL | ID MODEL | NOM CFM | ARI REF # |
Published Date: 06/03/2025 |
COOLING PERFORMANCE AT INDOOR DRY BULB TEMPERATURES
< font size="3"> OD AMB |
|
85 |
|
95 |
|
105 |
|
115 |
|
USE THE FOLLOWING FACTORS TO COMPENSATE FOR DIFFERENT AIR FLOW
AIR FLOW RATE, CFM.< /font> | CAPACITY MULTIPLIER | TOTAL POWER MULTIPLIER |
1550 | 0.98 | 0.99 |
1975 | 1.02 | 1.01 |
ARI RATING FOR COOLING
CFM | CAPACITY (A) TEST | SEER2 | EER2 |
1570 | 55500 | 14.60 | 12.00 |
A.R.I. Standard Capacity Rating Conditions |
< font size="1">A.R.I. STANDARD 210/240 RATING CONDITIONS — (A) Cooling 80°F. D.B., 67°F. W.B. air entering indoor coil, 95°F. D.B. air entering outdoor coil. (B) High Temperature Heating 47°F. D.B., 43°F. W.B. air entering outdoor coil, 70°F. D.B. air entering indoor coil. (C) Low Temperature Heating 17°F. D.B. ,15°F. W.B. air entering outdoor coil, 70°F. D.B. air entering indoor coil. (D) Rated indoor airflow for heating is the same as for cooling. |
OD MODEL | ID MODEL | NOM CFM | ARI REF # |
Published Date: 06/03/2025 |
HEATING PERFORMANCE AT INDOOR DRY BULB TEMPERATURE
TOTAL CAPACITY MBH. | TOTAL POWER IN KILOWATTS | OD AMB | 60 | 70 | 75 | 80 | 60 | 70 | 75 | 80 |
2 | 28.00 | 27.50 | 27.20 | 27.00 | 3.80 | 3.99 | 4.09 | 4.19 |
7 | 31.30 | 30.70 | 30.40 | 30.10 | 3.83 | 4.03 | 4.13 | 4.23 |
12 | 34.60 | 33.90 | 33.60 | 33.30 | 3.87 | 4.07 | 4.17 | 4.27 |
17 | 37.80 | 37.10 | 36.80 | 36.40 | 3.90 | 4.10 | 4.20 | 4.30 |
22 | 39.70 | 39.00 | 38.60 | 38.20 | 3.91 | 4.12 | 4.22 | 4.32 |
27 | 41.60 | 40.80 | 40.50 | 40.10 | 3.93 | 4.13 | 4.23 | 4.33 |
32 | 43.50 | 42.70 | 42.30 | 41.90 | 3.94 | 4.14 | 4.24 | 4.35 |
37 | 46.80 | 45.90 | 45.50 | 45.00 | 3.97 | 4.18 | 4.28 | 4.38 |
42 | 52.10 | 51.20 | 50.70 | 50.20 | 4.04 | 4.25 | 4.35 | 4.46 |
47 | 57.50 | 56.40 | 55.90 | 55.30 | 4.10 | 4.32 | 4.42 | 4.53 |
52 | 60.80 | 59.60 | 59.00 | 58.50 | 4.14 | 4.35 | 4.46 | 4.57 |
57 | 64.00 | 62.80 | 62.20 | 61.60 | 4.17 | 4.39 | 4.50 | 4.61 |
62 | 67.30 | 66.00 | 65.40 | 64.80 | 4.20 | 4.42 | 4.53 | 4.64 |
67 | 70.60 | 69.30 | 68.60 | 67.90 | 4.24 | 4.46 | 4.57 | 4.68 |
72 | 73.90 | 72.50 | 71.80 | 71.10 | 4.27 | 4.50 | 4.61 | 4.72 |
USE THE FOLLOWING FACTORS TO COMPENSATE FOR DIFFERENT AIR FLOW
AIR FLOW RATE, CFM.< /font> | CAPACITY MULTIPLIER | TOTAL POWER MULTIPLIER |
1750 | 0.99 | 0.98 |
2250 | 1.01 | 1.03 |
ARI RATING FOR HEATING
CFM | CAPACITY 47 | COP 47 | CAPACITY 17 | HSPF2 | |
1570 | 55000 | 3.90 | 36200 | 2.70 | 7.80 |
A.R.I. Standard Capacity Rating Conditions |
< font size="1">A.R.I. STANDARD 210/240 RATING CONDITIONS — (A) Cooling 80°F. D.B., 67°F. W.B. air entering indoor coil, 95°F. D.B. air entering outdoor coil. (B) High Temperature Heating 47°F. D.B., 43°F. W.B. air entering outdoor coil, 70°F. D.B. air entering indoor coil. (C) Low Temperature Heating 17°F. D.B. ,15°F. W.B. air entering outdoor coil, 70°F. D.B. air entering indoor coil. (D) Rated indoor airflow for heating is the same as for cooling. |