OD MODEL
4TWR4060N1

ID MODEL
TEM6B0C60H51+TDR

NOM CFM
1760

ARI REF #
209469929

Published Date: 06/03/2025

COOLING PERFORMANCE AT INDOOR DRY BULB TEMPERATURES

< font size="3"> OD AMB
ID WBTOT CAP72757880KW
85
5953.7043.4048.753.7053.403.98
6356.3035.6040.846.0049.504.02
6760.2028.1033.438.6042.104.06
7165.3021.0026.231.4034.904.09
95
5950.6042.0047.350.6050.604.47
6353.1034.2039.544.7048.204.51
6756.7026.8032.137.2040.704.56
7161.5019.6024.930.1033.604.60
105
5947.5040.6045.847.5047.504.96
6349.8032.9038.143.3046.805.01
6753.2025.5030.735.9039.405.06
7157.8018.3023.628.8032.305.11
115
5944.4039.2043.644.4044.405.45
6346.6031.6036.842.0045.505.51
6749.8024.2029.534.6038.105.56
7154.0017.0022.327.5031.005.61

USE THE FOLLOWING FACTORS TO COMPENSATE FOR DIFFERENT AIR FLOW

AIR FLOW RATE, CFM.< /font>CAPACITY MULTIPLIERTOTAL POWER MULTIPLIER
15500.980.99
19751.021.01

ARI RATING FOR COOLING

CFMCAPACITY (A) TESTSEER2EER2
15705550014.6012.00

A.R.I. Standard Capacity Rating Conditions

< font size="1">A.R.I. STANDARD 210/240 RATING CONDITIONS — (A) Cooling 80°F. D.B., 67°F. W.B. air entering indoor coil, 95°F. D.B. air entering outdoor coil. (B) High Temperature Heating 47°F. D.B., 43°F. W.B. air entering outdoor coil, 70°F. D.B. air entering indoor coil. (C) Low Temperature Heating 17°F. D.B. ,15°F. W.B. air entering outdoor coil, 70°F. D.B. air entering indoor coil. (D) Rated indoor airflow for heating is the same as for cooling.

 

 

 

OD MODEL
4TWR4060N1

ID MODEL
TEM6B0C60H51+TDR

NOM CFM
2000

ARI REF #
209469929

Published Date: 06/03/2025

HEATING PERFORMANCE AT INDOOR DRY BULB TEMPERATURE

< tr>
 TOTAL CAPACITY MBH.TOTAL POWER IN KILOWATTS
OD AMB6070758060707580
228.0027.5027.2027.003.803.994.094.19
731.3030.7030.4030.103.834.034.134.23
1234.6033.9033.6033.303.874.074.174.27
1737.8037.1036.8036.403.904.104.204.30
2239.7039.0038.6038.203.914.124.224.32
2741.6040.8040.5040.103.934.134.234.33
3243.5042.7042.3041.903.944.144.244.35
3746.8045.9045.5045.003.974.184.284.38
4252.1051.2050.7050.204.044.254.354.46
4757.5056.4055.9055.304.104.324.424.53
5260.8059.6059.0058.504.144.354.464.57
5764.0062.8062.2061.604.174.394.504.61
6267.3066.0065.4064.804.204.424.534.64
6770.6069.3068.6067.904.244.464.574.68
7273.9072.5071.8071.104.274.504.614.72

USE THE FOLLOWING FACTORS TO COMPENSATE FOR DIFFERENT AIR FLOW

AIR FLOW RATE, CFM.< /font>CAPACITY MULTIPLIERTOTAL POWER MULTIPLIER
17500.990.98
22501.011.03

ARI RATING FOR HEATING

CFMCAPACITY 47COP 47CAPACITY 17COP 17HSPF2
1570550003.90362002.707.80

A.R.I. Standard Capacity Rating Conditions

< font size="1">A.R.I. STANDARD 210/240 RATING CONDITIONS — (A) Cooling 80°F. D.B., 67°F. W.B. air entering indoor coil, 95°F. D.B. air entering outdoor coil. (B) High Temperature Heating 47°F. D.B., 43°F. W.B. air entering outdoor coil, 70°F. D.B. air entering indoor coil. (C) Low Temperature Heating 17°F. D.B. ,15°F. W.B. air entering outdoor coil, 70°F. D.B. air entering indoor coil. (D) Rated indoor airflow for heating is the same as for cooling.