OD MODEL
4TTR6048J1

ID MODEL
4PXADD60BS3

FURNACE
S9X1D120D5PSB

NOM CFM
1400

ARI REF #
203516801a

Published Date: 05/08/2025

COOLING PERFORMANCE AT INDOOR DRY BULB TEMPERATURES

< font size="3"> OD AMB
ID WBTOT CAP72757880KW
85
5943.3033.8037.741.4040.903.01
6345.4027.9031.835.7038.303.03
6748.5022.3026.230.1032.703.06
7152.7017.0020.924.8027.403.09
95
5940.6032.6036.540.4040.603.59
6342.5026.7030.634.5037.103.62
6745.5021.2025.129.0031.603.65
7149.3015.8019.723.6026.203.69
105
5937.8031.3035.237.8037.804.16
6339.7025.6029.533.4036.004.20
6742.4020.0023.927.8030.404.25
7146.0014.6018.522.4025.104.29
115
5935.1030.1033.935.1035.104.74
6336.8024.4028.332.2034.804.79
6739.3018.8022.726.6029.304.84
7142.6013.5017.421.3023.904.88

USE THE FOLLOWING FACTORS TO COMPENSATE FOR DIFFERENT AIR FLOW

AIR FLOW RATE, CFM.< /font>CAPACITY MULTIPLIERTOTAL POWER MULTIPLIER
12250.980.99
15751.021.01

ARI RATING FOR COOLING

CFMCAPACITY (A) TESTSEER2EER2
12504450015.2012.00

A.R.I. Standard Capacity Rating Conditions

< font size="1">A.R.I. STANDARD 210/240 RATING CONDITIONS — (A) Cooling 80°F. D.B., 67°F. W.B. air entering indoor coil, 95°F. D.B. air entering outdoor coil. (B) High Temperature Heating 47°F. D.B., 43°F. W.B. air entering outdoor coil, 70°F. D.B. air entering indoor coil. (C) Low Temperature Heating 17°F. D.B. ,15°F. W.B. air entering outdoor coil, 70°F. D.B. air entering indoor coil. (D) Rated indoor airflow for heating is the same as for cooling.