OD MODEL | ID MODEL | FURNACE | NOM CFM | ARI REF # |
Published Date: 12/07/2022 |
COOLING PERFORMANCE AT INDOOR DRY BULB TEMPERATURES
OD AMB |
|
85 |
|
95 |
|
105 |
|
115 |
|
USE THE FOLLOWING FACTORS TO COMPENSATE FOR DIFFERENT AIR FLOW
AIR FLOW RATE, CFM. | CAPACITY MULTIPLIER | TOTAL POWER MULTIPLIER |
1050 | 0.98 | 0.99 |
1350 | 1.02 | 1.01 |
ARI RATING FOR COOLING
CFM | CAPACITY (A) TEST | SEER | EER |
1165 | 37800 | 17.50 | 13.00 |
A.R.I. Standard Capacity Rating Conditions |
A.R.I. STANDARD 210/240 RATING CONDITIONS — (A) Cooling 80°F. D.B., 67°F. W.B. air entering indoor coil, 95°F. D.B. air entering outdoor coil. (B) High Temperature Heating 47°F. D.B., 43°F. W.B. air entering outdoor coil, 70°F. D.B. air entering indoor coil. (C) Low Temperature Heating 17°F. D.B. ,15°F. W.B. air entering outdoor coil, 70°F. D.B. air entering indoor coil. (D) Rated indoor airflow for heating is the same as for cooling. |
OD MODEL | ID MODEL | FURNACE | NOM CFM | ARI REF # |
Published Date: 12/07/2022 |
HEATING PERFORMANCE AT INDOOR DRY BULB TEMPERATURE
TOTAL CAPACITY MBH. | TOTAL POWER IN KILOWATTS | |||||||
OD AMB | 60 | 70 | 75 | 80 | 60 | 70 | 75 | 80 |
2 | 15.70 | 15.40 | 15.30 | 15.10 | 2.17 | 2.28 | 2.34 | 2.39 |
7 | 17.80 | 17.50 | 17.30 | 17.20 | 2.19 | 2.31 | 2.36 | 2.42 |
12 | 19.90 | 19.60 | 19.40 | 19.20 | 2.22 | 2.33 | 2.39 | 2.44 |
17 | 22.10 | 21.60 | 21.40 | 21.20 | 2.24 | 2.36 | 2.41 | 2.47 |
22 | 23.30 | 22.90 | 22.70 | 22.50 | 2.25 | 2.37 | 2.42 | 2.48 |
27 | 24.60 | 24.20 | 23.90 | 23.70 | 2.26 | 2.38 | 2.44 | 2.49 |
32 | 25.90 | 25.40 | 25.20 | 24.90 | 2.27 | 2.39 | 2.45 | 2.51 |
37 | 28.00 | 27.50 | 27.20 | 27.00 | 2.30 | 2.41 | 2.47 | 2.53 |
42 | 31.40 | 30.80 | 30.50 | 30.20 | 2.34 | 2.46 | 2.52 | 2.58 |
47 | 34.70 | 34.10 | 33.70 | 33.40 | 2.38 | 2.50 | 2.56 | 2.63 |
52 | 36.80 | 36.10 | 35.80 | 35.50 | 2.40 | 2.53 | 2.59 | 2.65 |
57 | 38.90 | 38.20 | 37.80 | 37.50 | 2.43 | 2.55 | 2.62 | 2.68 |
62 | 41.10 | 40.30 | 39.90 | 39.50 | 2.45 | 2.58 | 2.64 | 2.70 |
67 | 43.20 | 42.40 | 42.00 | 41.50 | 2.47 | 2.60 | 2.67 | 2.73 |
72 | 45.30 | 44.40 | 44.00 | 43.60 | 2.49 | 2.63 | 2.69 | 2.76 |
USE THE FOLLOWING FACTORS TO COMPENSATE FOR DIFFERENT AIR FLOW
AIR FLOW RATE, CFM. | CAPACITY MULTIPLIER | TOTAL POWER MULTIPLIER |
1050 | 0.99 | 0.98 |
1350 | 1.01 | 1.03 |
ARI RATING FOR HEATING
CFM | CAPACITY 47 | COP 47 | CAPACITY 17 | COP 17 | HSPF |
1165 | 34000 | 4.00 | 21600 | 2.70 | 8.50 |
A.R.I. Standard Capacity Rating Conditions |
A.R.I. STANDARD 210/240 RATING CONDITIONS — (A) Cooling 80°F. D.B., 67°F. W.B. air entering indoor coil, 95°F. D.B. air entering outdoor coil. (B) High Temperature Heating 47°F. D.B., 43°F. W.B. air entering outdoor coil, 70°F. D.B. air entering indoor coil. (C) Low Temperature Heating 17°F. D.B. ,15°F. W.B. air entering outdoor coil, 70°F. D.B. air entering indoor coil. (D) Rated indoor airflow for heating is the same as for cooling. |
LOW STAGE |
OD MODEL | ID MODEL | FURNACE | NOM CFM | ARI REF # |
Published Date: 12/07/2022 |
COOLING PERFORMANCE AT INDOOR DRY BULB TEMPERATURES
OD AMB |
|
75 |
|
85 |
|
90 |
|
95 |
|
USE THE FOLLOWING FACTORS TO COMPENSATE FOR DIFFERENT AIR FLOW
AIR FLOW RATE, CFM. | CAPACITY MULTIPLIER | TOTAL POWER MULTIPLIER |
875 | 0.98 | 0.99 |
1125 | 1.02 | 1.01 |
ARI RATING FOR COOLING
CFM | CAPACITY (A) TEST | SEER | EER |
1165 | 27717 | 17.50 | 13.00 |
A.R.I. Standard Capacity Rating Conditions |
A.R.I. STANDARD 210/240 RATING CONDITIONS — (A) Cooling 80°F. D.B., 67°F. W.B. air entering indoor coil, 95°F. D.B. air entering outdoor coil. (B) High Temperature Heating 47°F. D.B., 43°F. W.B. air entering outdoor coil, 70°F. D.B. air entering indoor coil. (C) Low Temperature Heating 17°F. D.B. ,15°F. W.B. air entering outdoor coil, 70°F. D.B. air entering indoor coil. (D) Rated indoor airflow for heating is the same as for cooling. |
LOW STAGE |
OD MODEL | ID MODEL | FURNACE | NOM CFM | ARI REF # |
Published Date: 12/07/2022 |
HEATING PERFORMANCE AT INDOOR DRY BULB TEMPERATURE
TOTAL CAPACITY MBH. | TOTAL POWER IN KILOWATTS | |||||||
OD AMB | 60 | 70 | 75 | 80 | 60 | 70 | 75 | 80 |
22 | 16.20 | 15.90 | 15.70 | 15.60 | 1.78 | 1.87 | 1.92 | 1.96 |
27 | 17.40 | 17.00 | 16.90 | 16.70 | 1.77 | 1.86 | 1.91 | 1.96 |
32 | 18.60 | 18.20 | 18.00 | 17.90 | 1.76 | 1.86 | 1.90 | 1.95 |
37 | 20.40 | 20.00 | 19.80 | 19.60 | 1.77 | 1.86 | 1.91 | 1.95 |
42 | 23.00 | 22.60 | 22.40 | 22.20 | 1.79 | 1.88 | 1.93 | 1.97 |
47 | 25.70 | 25.20 | 25.00 | 24.80 | 1.81 | 1.90 | 1.95 | 2.00 |
52 | 27.50 | 27.00 | 26.70 | 26.50 | 1.81 | 1.90 | 1.95 | 2.00 |
57 | 29.30 | 28.70 | 28.50 | 28.20 | 1.81 | 1.91 | 1.96 | 2.00 |
62 | 31.10 | 30.50 | 30.20 | 29.90 | 1.82 | 1.91 | 1.96 | 2.01 |
67 | 32.90 | 32.30 | 32.00 | 31.60 | 1.82 | 1.92 | 1.96 | 2.01 |
72 | 34.70 | 34.00 | 33.70 | 33.40 | 1.82 | 1.92 | 1.97 | 2.02 |
USE THE FOLLOWING FACTORS TO COMPENSATE FOR DIFFERENT AIR FLOW
AIR FLOW RATE, CFM. | CAPACITY MULTIPLIER | TOTAL POWER MULTIPLIER |
875 | 0.99 | 0.98 |
1125 | 1.01 | 1.03 |
ARI RATING FOR HEATING
CFM | CAPACITY 47 | COP 47 | CAPACITY 17 | COP 17 | HSPF |
1165 | 34000 | 4.00 | 21600 | 2.70 | 8.50 |
A.R.I. Standard Capacity Rating Conditions |
A.R.I. STANDARD 210/240 RATING CONDITIONS — (A) Cooling 80°F. D.B., 67°F. W.B. air entering indoor coil, 95°F. D.B. air entering outdoor coil. (B) High Temperature Heating 47°F. D.B., 43°F. W.B. air entering outdoor coil, 70°F. D.B. air entering indoor coil. (C) Low Temperature Heating 17°F. D.B. ,15°F. W.B. air entering outdoor coil, 70°F. D.B. air entering indoor coil. (D) Rated indoor airflow for heating is the same as for cooling. |