OD MODEL
4TWR6018H1

ID MODEL
TEM6A0B24H21+TDR

NOM CFM
600

ARI REF #
8937191

Published Date: 12/07/2022

COOLING PERFORMANCE AT INDOOR DRY BULB TEMPERATURES

OD AMB
ID WBTOT CAP72757880KW
85
5918.4015.2017.118.4018.401.20
6319.3012.5014.416.2017.401.21
6720.609.9011.713.6014.801.22
7122.407.409.211.1012.301.23
95
5917.1014.7016.517.1017.101.46
6317.9011.9013.815.6016.801.47
6719.109.3011.213.0014.201.49
7120.706.808.610.5011.701.50
105
5915.7014.0015.515.7015.701.72
6316.4011.3013.215.0016.201.74
6717.608.7010.612.4013.601.76
7119.106.208.19.9011.101.77
115
5914.3013.4014.314.3014.301.98
6315.0010.7012.614.4015.002.00
6716.008.1010.011.8013.102.02
7117.405.707.59.3010.602.04

USE THE FOLLOWING FACTORS TO COMPENSATE FOR DIFFERENT AIR FLOW

AIR FLOW RATE, CFM.CAPACITY MULTIPLIERTOTAL POWER MULTIPLIER
5250.980.99
6751.021.01

ARI RATING FOR COOLING

CFMCAPACITY (A) TESTSEEREER
5501880016.0012.50

A.R.I. Standard Capacity Rating Conditions

A.R.I. STANDARD 210/240 RATING CONDITIONS — (A) Cooling 80°F. D.B., 67°F. W.B. air entering indoor coil, 95°F. D.B. air entering outdoor coil. (B) High Temperature Heating 47°F. D.B., 43°F. W.B. air entering outdoor coil, 70°F. D.B. air entering indoor coil. (C) Low Temperature Heating 17°F. D.B. ,15°F. W.B. air entering outdoor coil, 70°F. D.B. air entering indoor coil. (D) Rated indoor airflow for heating is the same as for cooling.

 

 

 

 

OD MODEL
4TWR6018H1

ID MODEL
TEM6A0B24H21+TDR

NOM CFM
600

ARI REF #
8937191

Published Date: 12/07/2022

HEATING PERFORMANCE AT INDOOR DRY BULB TEMPERATURE

 TOTAL CAPACITY MBH.TOTAL POWER IN KILOWATTS
OD AMB6070758060707580
26.806.706.606.501.151.211.241.27
77.907.807.707.601.161.221.251.28
129.108.908.908.801.171.231.261.29
1710.3010.1010.009.901.181.241.271.30
2211.0010.8010.7010.601.181.241.271.30
2711.8011.6011.5011.401.181.251.281.31
3212.6012.3012.2012.101.191.251.281.31
3713.7013.5013.3013.201.201.261.291.32
4215.5015.2015.1014.901.221.281.311.34
4717.3016.9016.8016.601.241.301.331.37
5218.4018.1017.9017.701.251.311.341.38
5719.6019.2019.0018.901.261.321.361.39
6220.7020.4020.2020.001.271.331.371.40
6721.9021.5021.3021.101.271.341.381.41
7223.1022.6022.4022.201.281.351.391.42

USE THE FOLLOWING FACTORS TO COMPENSATE FOR DIFFERENT AIR FLOW

AIR FLOW RATE, CFM.CAPACITY MULTIPLIERTOTAL POWER MULTIPLIER
5250.990.98
6751.011.03

ARI RATING FOR HEATING

CFMCAPACITY 47COP 47CAPACITY 17COP 17HSPF
550168003.84100002.409.00

A.R.I. Standard Capacity Rating Conditions

A.R.I. STANDARD 210/240 RATING CONDITIONS — (A) Cooling 80°F. D.B., 67°F. W.B. air entering indoor coil, 95°F. D.B. air entering outdoor coil. (B) High Temperature Heating 47°F. D.B., 43°F. W.B. air entering outdoor coil, 70°F. D.B. air entering indoor coil. (C) Low Temperature Heating 17°F. D.B. ,15°F. W.B. air entering outdoor coil, 70°F. D.B. air entering indoor coil. (D) Rated indoor airflow for heating is the same as for cooling.