OD MODEL | ID MODEL | NOM CFM | ARI REF # |
Published Date: 12/07/2022 |
COOLING PERFORMANCE AT INDOOR DRY BULB TEMPERATURES
OD AMB |
|
85 |
|
95 |
|
105 |
|
115 |
|
USE THE FOLLOWING FACTORS TO COMPENSATE FOR DIFFERENT AIR FLOW
AIR FLOW RATE, CFM. | CAPACITY MULTIPLIER | TOTAL POWER MULTIPLIER |
1100 | 0.98 | 0.99 |
1425 | 1.02 | 1.01 |
ARI RATING FOR COOLING
CFM | CAPACITY (A) TEST | SEER | EER |
1115 | 41000 | 14.50 | 12.00 |
A.R.I. Standard Capacity Rating Conditions |
A.R.I. STANDARD 210/240 RATING CONDITIONS — (A) Cooling 80°F. D.B., 67°F. W.B. air entering indoor coil, 95°F. D.B. air entering outdoor coil. (B) High Temperature Heating 47°F. D.B., 43°F. W.B. air entering outdoor coil, 70°F. D.B. air entering indoor coil. (C) Low Temperature Heating 17°F. D.B. ,15°F. W.B. air entering outdoor coil, 70°F. D.B. air entering indoor coil. (D) Rated indoor airflow for heating is the same as for cooling. |
OD MODEL | ID MODEL | NOM CFM | ARI REF # |
Published Date: 12/07/2022 |
HEATING PERFORMANCE AT INDOOR DRY BULB TEMPERATURE
TOTAL CAPACITY MBH. | TOTAL POWER IN KILOWATTS | |||||||
OD AMB | 60 | 70 | 75 | 80 | 60 | 70 | 75 | 80 |
2 | 18.90 | 18.50 | 18.40 | 18.20 | 2.58 | 2.72 | 2.78 | 2.85 |
7 | 21.00 | 20.60 | 20.40 | 20.20 | 2.62 | 2.76 | 2.83 | 2.90 |
12 | 23.10 | 22.70 | 22.50 | 22.30 | 2.66 | 2.80 | 2.87 | 2.94 |
17 | 25.20 | 24.80 | 24.50 | 24.30 | 2.70 | 2.84 | 2.91 | 2.98 |
22 | 26.50 | 26.00 | 25.70 | 25.50 | 2.72 | 2.87 | 2.94 | 3.01 |
27 | 27.70 | 27.10 | 26.90 | 26.60 | 2.74 | 2.89 | 2.96 | 3.03 |
32 | 28.90 | 28.30 | 28.10 | 27.80 | 2.77 | 2.91 | 2.99 | 3.06 |
37 | 31.00 | 30.40 | 30.10 | 29.80 | 2.81 | 2.95 | 3.03 | 3.10 |
42 | 34.50 | 33.80 | 33.50 | 33.20 | 2.87 | 3.02 | 3.10 | 3.17 |
47 | 38.00 | 37.30 | 36.90 | 36.60 | 2.93 | 3.09 | 3.17 | 3.25 |
52 | 40.10 | 39.30 | 39.00 | 38.60 | 2.97 | 3.13 | 3.21 | 3.29 |
57 | 42.20 | 41.40 | 41.00 | 40.60 | 3.01 | 3.17 | 3.25 | 3.33 |
62 | 44.30 | 43.50 | 43.10 | 42.70 | 3.05 | 3.21 | 3.29 | 3.38 |
67 | 46.50 | 45.60 | 45.20 | 44.70 | 3.09 | 3.25 | 3.34 | 3.42 |
72 | 48.60 | 47.70 | 47.20 | 46.80 | 3.13 | 3.30 | 3.38 | 3.46 |
USE THE FOLLOWING FACTORS TO COMPENSATE FOR DIFFERENT AIR FLOW
AIR FLOW RATE, CFM. | CAPACITY MULTIPLIER | TOTAL POWER MULTIPLIER |
1225 | 0.99 | 0.98 |
1575 | 1.01 | 1.03 |
ARI RATING FOR HEATING
CFM | CAPACITY 47 | COP 47 | CAPACITY 17 | COP 17 | HSPF |
1115 | 36400 | 3.60 | 24200 | 2.60 | 8.50 |
A.R.I. Standard Capacity Rating Conditions |
A.R.I. STANDARD 210/240 RATING CONDITIONS — (A) Cooling 80°F. D.B., 67°F. W.B. air entering indoor coil, 95°F. D.B. air entering outdoor coil. (B) High Temperature Heating 47°F. D.B., 43°F. W.B. air entering outdoor coil, 70°F. D.B. air entering indoor coil. (C) Low Temperature Heating 17°F. D.B. ,15°F. W.B. air entering outdoor coil, 70°F. D.B. air entering indoor coil. (D) Rated indoor airflow for heating is the same as for cooling. |