OD MODEL
4TWR5049E1

ID MODEL
TEM6A0C48H41+TDR+UF/HRZ

NOM CFM
1600

ARI REF #
8875426(D)

Published Date: 11/04/2018

COOLING PERFORMANCE AT INDOOR DRY BULB TEMPERATURES

OD AMB
ID WBTOT CAP72757880KW
85
5947.2038.3042.947.2047.203.39
6349.5031.4036.040.6043.603.43
6752.9024.9029.534.1037.103.46
7157.4018.7023.327.8030.903.49
95
5943.8036.8041.343.8043.803.71
6345.9030.0034.539.1042.103.75
6749.0023.5028.132.6035.603.78
7153.2017.2021.826.4029.403.82
105
5940.3035.2039.340.3040.304.03
6342.3028.5033.137.6040.704.07
6745.2022.0026.631.2034.204.11
7149.0015.8020.424.9028.004.15
115
5936.9033.7036.936.9036.904.34
6338.7027.1031.636.2038.704.39
6741.3020.6025.229.8032.804.43
7144.8014.4019.023.5026.604.47

USE THE FOLLOWING FACTORS TO COMPENSATE FOR DIFFERENT AIR FLOW

AIR FLOW RATE, CFM.CAPACITY MULTIPLIERTOTAL POWER MULTIPLIER
14000.980.99
18001.021.01

ARI RATING FOR COOLING

CFMCAPACITY (A) TESTSEEREER
14304800015.0012.50

A.R.I. Standard Capacity Rating Conditions

A.R.I. STANDARD 210/240 RATING CONDITIONS — (A) Cooling 80°F. D.B., 67°F. W.B. air entering indoor coil, 95°F. D.B. air entering outdoor coil. (B) High Temperature Heating 47°F. D.B., 43°F. W.B. air entering outdoor coil, 70°F. D.B. air entering indoor coil. (C) Low Temperature Heating 17°F. D.B. ,15°F. W.B. air entering outdoor coil, 70°F. D.B. air entering indoor coil. (D) Rated indoor airflow for heating is the same as for cooling.

 

 

 

 

OD MODEL
4TWR5049E1

ID MODEL
TEM6A0C48H41+TDR+UF/HRZ

NOM CFM
1600

ARI REF #
8875426(D)

Published Date: 11/04/2018

HEATING PERFORMANCE AT INDOOR DRY BULB TEMPERATURE

 TOTAL CAPACITY MBH.TOTAL POWER IN KILOWATTS
OD AMB6070758060707580
222.8022.3022.1021.902.953.113.193.27
725.6025.1024.9024.703.003.163.233.31
1228.5027.9027.7027.403.043.203.283.36
1731.3030.7030.4030.103.083.243.333.41
2233.0032.4032.1031.803.113.273.353.44
2734.7034.0033.7033.403.133.303.383.46
3236.4035.7035.4035.003.163.323.413.49
3739.2038.5038.1037.803.203.373.453.54
4243.8043.0042.6042.203.273.443.533.62
4748.4047.5047.0046.603.333.513.603.69
5251.3050.3049.8049.303.373.563.653.74
5754.1053.1052.6052.103.423.603.693.79
6257.0055.9055.4054.803.463.653.743.83
6759.8058.7058.1057.603.503.693.793.88
7262.7061.5060.9060.303.543.743.833.93

USE THE FOLLOWING FACTORS TO COMPENSATE FOR DIFFERENT AIR FLOW

AIR FLOW RATE, CFM.CAPACITY MULTIPLIERTOTAL POWER MULTIPLIER
14000.990.98
18001.011.03

ARI RATING FOR HEATING

CFMCAPACITY 47COP 47CAPACITY 17COP 17HSPF
1430470004.00304002.809.50

A.R.I. Standard Capacity Rating Conditions

A.R.I. STANDARD 210/240 RATING CONDITIONS — (A) Cooling 80°F. D.B., 67°F. W.B. air entering indoor coil, 95°F. D.B. air entering outdoor coil. (B) High Temperature Heating 47°F. D.B., 43°F. W.B. air entering outdoor coil, 70°F. D.B. air entering indoor coil. (C) Low Temperature Heating 17°F. D.B. ,15°F. W.B. air entering outdoor coil, 70°F. D.B. air entering indoor coil. (D) Rated indoor airflow for heating is the same as for cooling.