OD MODEL
4TTR3048D1

ID MODEL
4GXCC007AC6HUA

FURNACE
TUD2C100ACV5

NOM CFM
1300

ARI REF #
8787455

Published Date: 12/07/2022

COOLING PERFORMANCE AT INDOOR DRY BULB TEMPERATURES

OD AMB
ID WBTOT CAP72757880KW
85
5943.234.3138.642.943.23.61
6345.928.1832.536.7739.643.62
6748.821.9926.330.5733.443.62
7151.815.6920.024.2727.143.64
95
5940.833.137.440.840.83.99
6343.427.0131.335.638.474
6746.220.8625.229.4532.324.02
7149.114.6118.923.1926.054.04
105
5938.231.8236.238.238.24.41
6340.825.8130.134.4137.284.43
6743.419.6624.028.2531.124.45
7146.213.4517.822.0424.94.48
115
5935.530.534.535.535.54.9
6337.924.4928.833.0935.964.92
6740.418.3822.726.9729.844.95
7143.112.2216.620.8123.684.98

USE THE FOLLOWING FACTORS TO COMPENSATE FOR DIFFERENT AIR FLOW

AIR FLOW RATE, CFM.CAPACITY MULTIPLIERTOTAL POWER MULTIPLIER
11400.980.99
14651.021.01

ARI RATING FOR COOLING

CFMCAPACITY (A) TESTSEEREER
13004550013.5011.50

A.R.I. Standard Capacity Rating Conditions

A.R.I. STANDARD 210/240 RATING CONDITIONS — (A) Cooling 80°F. D.B., 67°F. W.B. air entering indoor coil, 95°F. D.B. air entering outdoor coil. (B) High Temperature Heating 47°F. D.B., 43°F. W.B. air entering outdoor coil, 70°F. D.B. air entering indoor coil. (C) Low Temperature Heating 17°F. D.B. ,15°F. W.B. air entering outdoor coil, 70°F. D.B. air entering indoor coil. (D) Rated indoor airflow for heating is the same as for cooling.