OD MODEL
4TTR6060J1

ID MODEL
4TXCD010DS3

FURNACE
TUD2D120A9V5

NOM CFM
1780

ARI REF #
8736277

Published Date: 12/07/2022

COOLING PERFORMANCE AT INDOOR DRY BULB TEMPERATURES

OD AMB
ID WBTOT CAP72757880KW
85
5954.7044.3049.754.7054.303.94
6357.3036.3041.747.0050.503.98
6761.3028.7034.139.4042.904.01
7166.5021.4026.732.1035.604.05
95
5951.6042.9048.351.6051.604.37
6354.1035.0040.345.6049.204.41
6757.8027.4032.738.0041.604.45
7162.7020.0025.430.7034.304.49
105
5948.5041.5046.848.5048.504.80
6350.8033.6038.944.3047.804.85
6754.3026.0031.436.7040.304.89
7158.9018.7024.129.4033.004.94
115
5945.4040.1044.645.4045.405.23
6347.6032.3037.642.9046.505.28
6750.9024.8030.135.4039.005.33
7155.2017.5022.828.1031.705.38

USE THE FOLLOWING FACTORS TO COMPENSATE FOR DIFFERENT AIR FLOW

AIR FLOW RATE, CFM.CAPACITY MULTIPLIERTOTAL POWER MULTIPLIER
15500.980.99
20001.021.01

ARI RATING FOR COOLING

CFMCAPACITY (A) TESTSEEREER
15805650015.0012.50

A.R.I. Standard Capacity Rating Conditions

A.R.I. STANDARD 210/240 RATING CONDITIONS — (A) Cooling 80°F. D.B., 67°F. W.B. air entering indoor coil, 95°F. D.B. air entering outdoor coil. (B) High Temperature Heating 47°F. D.B., 43°F. W.B. air entering outdoor coil, 70°F. D.B. air entering indoor coil. (C) Low Temperature Heating 17°F. D.B. ,15°F. W.B. air entering outdoor coil, 70°F. D.B. air entering indoor coil. (D) Rated indoor airflow for heating is the same as for cooling.