OD MODEL
4TWB3036C1

ID MODEL
TMM5A0B36M31SA

NOM CFM
1150

ARI REF #
7849905

Published Date: 06/05/2019

COOLING PERFORMANCE AT INDOOR DRY BULB TEMPERATURES

OD AMB
ID WBTOT CAP72757880KW
85
593325.628.430.932.42.65
6335.022.425.828.730.52.67
6735.018.422.125.527.62.68
7135.013.717.621.423.82.7
95
5930.224.827.830.230.22.92
6333.121.625.028.230.22.94
6735.017.421.224.726.62.95
7135.012.816.720.522.92.97
105
5927.523.926.827.527.53.19
6330.320.524.127.429.53.21
6732.716.420.223.826.23.22
7134.61215.819.5223.24
115
5924.822.724.824.824.83.46
6327.619.423.026.427.63.48
6729.915.319.122.725.13.49
7131.811.114.718.420.93.51

USE THE FOLLOWING FACTORS TO COMPENSATE FOR DIFFERENT AIR FLOW

AIR FLOW RATE, CFM.CAPACITY MULTIPLIERTOTAL POWER MULTIPLIER
10050.980.99
12951.021.01

ARI RATING FOR COOLING

CFMCAPACITY (A) TESTSEEREER
11503500014.0012.00

A.R.I. Standard Capacity Rating Conditions

A.R.I. STANDARD 210/240 RATING CONDITIONS — (A) Cooling 80°F. D.B., 67°F. W.B. air entering indoor coil, 95°F. D.B. air entering outdoor coil. (B) High Temperature Heating 47°F. D.B., 43°F. W.B. air entering outdoor coil, 70°F. D.B. air entering indoor coil. (C) Low Temperature Heating 17°F. D.B. ,15°F. W.B. air entering outdoor coil, 70°F. D.B. air entering indoor coil. (D) Rated indoor airflow for heating is the same as for cooling.

 

 

 

 

OD MODEL
4TWB3036C1

ID MODEL
TMM5A0B36M31SA

NOM CFM
1150

ARI REF #
7849905

Published Date: 06/05/2019

HEATING PERFORMANCE AT INDOOR DRY BULB TEMPERATURE

 TOTAL CAPACITY MBH.TOTAL POWER IN KILOWATTS
OD AMB6070758060707580
215.2114.7914.9314.652.182.282.322.37
716.9316.4616.6216.32.242.332.382.43
1218.6818.1618.3417.992.292.392.442.49
1720.4820.119.9119.722.352.452.52.55
2222.3721.9421.7321.522.392.492.552.6
2724.2523.7823.5523.312.432.542.592.65
3225.7925.2725.0124.762.472.582.642.7
3728.3827.8227.5427.262.542.662.712.77
4232.0431.4331.1330.832.612.732.792.85
4735.035.035.034.752.672.82.862.93
5235.035.035.035.02.732.862.922.99
5735.035.035.035.02.782.922.983.05
6235.035.035.035.02.842.983.043.11
6735.035.035.035.02.893.033.13.17
7235.035.035.035.02.953.093.163.24

USE THE FOLLOWING FACTORS TO COMPENSATE FOR DIFFERENT AIR FLOW

AIR FLOW RATE, CFM.CAPACITY MULTIPLIERTOTAL POWER MULTIPLIER
10050.990.98
12951.011.03

ARI RATING FOR HEATING

CFMCAPACITY 47COP 47CAPACITY 17COP 17HSPF
1005350003.7200002.48.2

A.R.I. Standard Capacity Rating Conditions

A.R.I. STANDARD 210/240 RATING CONDITIONS — (A) Cooling 80°F. D.B., 67°F. W.B. air entering indoor coil, 95°F. D.B. air entering outdoor coil. (B) High Temperature Heating 47°F. D.B., 43°F. W.B. air entering outdoor coil, 70°F. D.B. air entering indoor coil. (C) Low Temperature Heating 17°F. D.B. ,15°F. W.B. air entering outdoor coil, 70°F. D.B. air entering indoor coil. (D) Rated indoor airflow for heating is the same as for cooling.