OD MODEL | ID MODEL | FURNACE | NOM CFM | ARI REF # |
Published Date: 06/05/2019 |
COOLING PERFORMANCE AT INDOOR DRY BULB TEMPERATURES
OD AMB |
|
85 |
|
95 |
|
105 |
|
115 |
|
USE THE FOLLOWING FACTORS TO COMPENSATE FOR DIFFERENT AIR FLOW
AIR FLOW RATE, CFM. | CAPACITY MULTIPLIER | TOTAL POWER MULTIPLIER |
1400 | 0.98 | 0.99 |
1800 | 1.02 | 1.01 |
ARI RATING FOR COOLING
CFM | CAPACITY (A) TEST | SEER | EER |
1470 | 48000 | 15.00 | 12.50 |
A.R.I. Standard Capacity Rating Conditions |
A.R.I. STANDARD 210/240 RATING CONDITIONS — (A) Cooling 80°F. D.B., 67°F. W.B. air entering indoor coil, 95°F. D.B. air entering outdoor coil. (B) High Temperature Heating 47°F. D.B., 43°F. W.B. air entering outdoor coil, 70°F. D.B. air entering indoor coil. (C) Low Temperature Heating 17°F. D.B. ,15°F. W.B. air entering outdoor coil, 70°F. D.B. air entering indoor coil. (D) Rated indoor airflow for heating is the same as for cooling. |
OD MODEL | ID MODEL | FURNACE | NOM CFM | ARI REF # |
Published Date: 06/05/2019 |
HEATING PERFORMANCE AT INDOOR DRY BULB TEMPERATURE
TOTAL CAPACITY MBH. | TOTAL POWER IN KILOWATTS | |||||||
OD AMB | 60 | 70 | 75 | 80 | 60 | 70 | 75 | 80 |
2 | 23.40 | 22.90 | 22.70 | 22.50 | 3.49 | 3.67 | 3.76 | 3.86 |
7 | 26.20 | 25.70 | 25.50 | 25.20 | 3.49 | 3.68 | 3.77 | 3.86 |
12 | 29.00 | 28.50 | 28.20 | 27.90 | 3.50 | 3.68 | 3.77 | 3.87 |
17 | 31.80 | 31.20 | 30.90 | 30.60 | 3.50 | 3.69 | 3.78 | 3.87 |
22 | 33.50 | 32.90 | 32.60 | 32.20 | 3.49 | 3.67 | 3.76 | 3.86 |
27 | 35.10 | 34.50 | 34.20 | 33.80 | 3.48 | 3.66 | 3.75 | 3.84 |
32 | 36.80 | 36.10 | 35.80 | 35.40 | 3.46 | 3.64 | 3.73 | 3.83 |
37 | 39.60 | 38.90 | 38.50 | 38.10 | 3.47 | 3.65 | 3.74 | 3.83 |
42 | 44.20 | 43.40 | 43.00 | 42.50 | 3.50 | 3.68 | 3.77 | 3.87 |
47 | 48.80 | 47.90 | 47.40 | 47.00 | 3.53 | 3.72 | 3.81 | 3.90 |
52 | 51.60 | 50.60 | 50.20 | 49.70 | 3.53 | 3.72 | 3.81 | 3.91 |
57 | 54.40 | 53.40 | 52.90 | 52.40 | 3.54 | 3.73 | 3.82 | 3.91 |
62 | 57.30 | 56.20 | 55.60 | 55.10 | 3.54 | 3.73 | 3.82 | 3.92 |
67 | 60.10 | 59.00 | 58.40 | 57.80 | 3.55 | 3.74 | 3.83 | 3.92 |
72 | 62.90 | 61.70 | 61.10 | 60.50 | 3.55 | 3.74 | 3.84 | 3.93 |
USE THE FOLLOWING FACTORS TO COMPENSATE FOR DIFFERENT AIR FLOW
AIR FLOW RATE, CFM. | CAPACITY MULTIPLIER | TOTAL POWER MULTIPLIER |
1400 | 0.99 | 0.98 |
1800 | 1.01 | 1.03 |
ARI RATING FOR HEATING
CFM | CAPACITY 47 | COP 47 | CAPACITY 17 | COP 17 | HSPF |
1470 | 47500 | 3.80 | 31000 | 2.50 | 8.55 |
A.R.I. Standard Capacity Rating Conditions |
A.R.I. STANDARD 210/240 RATING CONDITIONS — (A) Cooling 80°F. D.B., 67°F. W.B. air entering indoor coil, 95°F. D.B. air entering outdoor coil. (B) High Temperature Heating 47°F. D.B., 43°F. W.B. air entering outdoor coil, 70°F. D.B. air entering indoor coil. (C) Low Temperature Heating 17°F. D.B. ,15°F. W.B. air entering outdoor coil, 70°F. D.B. air entering indoor coil. (D) Rated indoor airflow for heating is the same as for cooling. |