OD MODEL | ID MODEL | FURNACE | NOM CFM | ARI REF # |
Published Date: 06/05/2019 |
COOLING PERFORMANCE AT INDOOR DRY BULB TEMPERATURES
OD AMB |
|
85 |
|
95 |
|
105 |
|
115 |
|
USE THE FOLLOWING FACTORS TO COMPENSATE FOR DIFFERENT AIR FLOW
AIR FLOW RATE, CFM. | CAPACITY MULTIPLIER | TOTAL POWER MULTIPLIER |
1400 | 0.98 | 0.99 |
1800 | 1.02 | 1.01 |
ARI RATING FOR COOLING
CFM | CAPACITY (A) TEST | SEER | EER |
1485 | 46500 | 14.50 | 11.50 |
A.R.I. Standard Capacity Rating Conditions |
A.R.I. STANDARD 210/240 RATING CONDITIONS — (A) Cooling 80°F. D.B., 67°F. W.B. air entering indoor coil, 95°F. D.B. air entering outdoor coil. (B) High Temperature Heating 47°F. D.B., 43°F. W.B. air entering outdoor coil, 70°F. D.B. air entering indoor coil. (C) Low Temperature Heating 17°F. D.B. ,15°F. W.B. air entering outdoor coil, 70°F. D.B. air entering indoor coil. (D) Rated indoor airflow for heating is the same as for cooling. |
OD MODEL | ID MODEL | FURNACE | NOM CFM | ARI REF # |
Published Date: 06/05/2019 |
HEATING PERFORMANCE AT INDOOR DRY BULB TEMPERATURE
TOTAL CAPACITY MBH. | TOTAL POWER IN KILOWATTS | |||||||
OD AMB | 60 | 70 | 75 | 80 | 60 | 70 | 75 | 80 |
2 | 23.90 | 23.50 | 23.20 | 23.00 | 3.43 | 3.61 | 3.70 | 3.79 |
7 | 26.30 | 25.80 | 25.50 | 25.30 | 3.42 | 3.60 | 3.69 | 3.78 |
12 | 28.60 | 28.10 | 27.80 | 27.50 | 3.42 | 3.59 | 3.68 | 3.77 |
17 | 31.00 | 30.40 | 30.10 | 29.80 | 3.41 | 3.58 | 3.67 | 3.76 |
22 | 32.20 | 31.60 | 31.30 | 31.00 | 3.38 | 3.56 | 3.64 | 3.73 |
27 | 33.50 | 32.90 | 32.60 | 32.30 | 3.35 | 3.53 | 3.62 | 3.70 |
32 | 34.80 | 34.10 | 33.80 | 33.50 | 3.33 | 3.50 | 3.59 | 3.67 |
37 | 37.10 | 36.40 | 36.10 | 35.70 | 3.32 | 3.49 | 3.58 | 3.66 |
42 | 41.10 | 40.40 | 40.00 | 39.60 | 3.34 | 3.51 | 3.60 | 3.68 |
47 | 45.10 | 44.30 | 43.90 | 43.40 | 3.35 | 3.53 | 3.62 | 3.70 |
52 | 47.50 | 46.60 | 46.20 | 45.70 | 3.35 | 3.52 | 3.61 | 3.69 |
57 | 49.90 | 48.90 | 48.50 | 48.00 | 3.34 | 3.51 | 3.60 | 3.68 |
62 | 52.20 | 51.20 | 50.70 | 50.30 | 3.33 | 3.50 | 3.59 | 3.67 |
67 | 54.60 | 53.60 | 53.00 | 52.50 | 3.32 | 3.49 | 3.58 | 3.66 |
72 | 56.90 | 55.90 | 55.30 | 54.80 | 3.31 | 3.48 | 3.57 | 3.65 |
USE THE FOLLOWING FACTORS TO COMPENSATE FOR DIFFERENT AIR FLOW
AIR FLOW RATE, CFM. | CAPACITY MULTIPLIER | TOTAL POWER MULTIPLIER |
1400 | 0.99 | 0.98 |
1800 | 1.01 | 1.03 |
ARI RATING FOR HEATING
CFM | CAPACITY 47 | COP 47 | CAPACITY 17 | COP 17 | HSPF |
1485 | 44000 | 3.70 | 30200 | 2.50 | 8.55 |
A.R.I. Standard Capacity Rating Conditions |
A.R.I. STANDARD 210/240 RATING CONDITIONS — (A) Cooling 80°F. D.B., 67°F. W.B. air entering indoor coil, 95°F. D.B. air entering outdoor coil. (B) High Temperature Heating 47°F. D.B., 43°F. W.B. air entering outdoor coil, 70°F. D.B. air entering indoor coil. (C) Low Temperature Heating 17°F. D.B. ,15°F. W.B. air entering outdoor coil, 70°F. D.B. air entering indoor coil. (D) Rated indoor airflow for heating is the same as for cooling. |