OD MODEL | ID MODEL | FURNACE | NOM CFM | ARI REF # |
Published Date: 06/05/2019 |
COOLING PERFORMANCE AT INDOOR DRY BULB TEMPERATURES
OD AMB |
|
85 |
|
95 |
|
105 |
|
115 |
|
USE THE FOLLOWING FACTORS TO COMPENSATE FOR DIFFERENT AIR FLOW
AIR FLOW RATE, CFM. | CAPACITY MULTIPLIER | TOTAL POWER MULTIPLIER |
1400 | 0.98 | 0.99 |
1800 | 1.02 | 1.01 |
ARI RATING FOR COOLING
CFM | CAPACITY (A) TEST | SEER | EER |
1475 | 49500 | 15.00 | 12.30 |
A.R.I. Standard Capacity Rating Conditions |
A.R.I. STANDARD 210/240 RATING CONDITIONS — (A) Cooling 80°F. D.B., 67°F. W.B. air entering indoor coil, 95°F. D.B. air entering outdoor coil. (B) High Temperature Heating 47°F. D.B., 43°F. W.B. air entering outdoor coil, 70°F. D.B. air entering indoor coil. (C) Low Temperature Heating 17°F. D.B. ,15°F. W.B. air entering outdoor coil, 70°F. D.B. air entering indoor coil. (D) Rated indoor airflow for heating is the same as for cooling. |
OD MODEL | ID MODEL | FURNACE | NOM CFM | ARI REF # |
Published Date: 06/05/2019 |
HEATING PERFORMANCE AT INDOOR DRY BULB TEMPERATURE
TOTAL CAPACITY MBH. | TOTAL POWER IN KILOWATTS | |||||||
OD AMB | 60 | 70 | 75 | 80 | 60 | 70 | 75 | 80 |
2 | 23.00 | 22.60 | 22.30 | 22.10 | 3.65 | 3.85 | 3.94 | 4.04 |
7 | 25.80 | 25.30 | 25.10 | 24.80 | 3.63 | 3.83 | 3.92 | 4.02 |
12 | 28.60 | 28.10 | 27.80 | 27.50 | 3.62 | 3.81 | 3.90 | 4.00 |
17 | 31.40 | 30.80 | 30.50 | 30.20 | 3.60 | 3.79 | 3.88 | 3.98 |
22 | 33.10 | 32.40 | 32.10 | 31.80 | 3.56 | 3.75 | 3.84 | 3.94 |
27 | 34.70 | 34.10 | 33.70 | 33.40 | 3.52 | 3.71 | 3.80 | 3.89 |
32 | 36.40 | 35.70 | 35.30 | 35.00 | 3.48 | 3.67 | 3.76 | 3.85 |
37 | 39.20 | 38.40 | 38.10 | 37.70 | 3.46 | 3.65 | 3.74 | 3.83 |
42 | 43.70 | 42.90 | 42.50 | 42.10 | 3.48 | 3.66 | 3.75 | 3.84 |
47 | 48.20 | 47.30 | 46.90 | 46.40 | 3.49 | 3.67 | 3.77 | 3.86 |
52 | 51.10 | 50.10 | 49.60 | 49.10 | 3.47 | 3.66 | 3.75 | 3.84 |
57 | 53.90 | 52.90 | 52.30 | 51.80 | 3.46 | 3.64 | 3.73 | 3.82 |
62 | 56.70 | 55.60 | 55.10 | 54.50 | 3.44 | 3.62 | 3.71 | 3.80 |
67 | 59.50 | 58.40 | 57.80 | 57.20 | 3.42 | 3.60 | 3.69 | 3.78 |
72 | 62.30 | 61.10 | 60.50 | 59.90 | 3.40 | 3.58 | 3.67 | 3.76 |
USE THE FOLLOWING FACTORS TO COMPENSATE FOR DIFFERENT AIR FLOW
AIR FLOW RATE, CFM. | CAPACITY MULTIPLIER | TOTAL POWER MULTIPLIER |
1400 | 0.99 | 0.98 |
1800 | 1.01 | 1.03 |
ARI RATING FOR HEATING
CFM | CAPACITY 47 | COP 47 | CAPACITY 17 | COP 17 | HSPF |
1475 | 47000 | 3.80 | 30600 | 2.40 | 8.20 |
A.R.I. Standard Capacity Rating Conditions |
A.R.I. STANDARD 210/240 RATING CONDITIONS — (A) Cooling 80°F. D.B., 67°F. W.B. air entering indoor coil, 95°F. D.B. air entering outdoor coil. (B) High Temperature Heating 47°F. D.B., 43°F. W.B. air entering outdoor coil, 70°F. D.B. air entering indoor coil. (C) Low Temperature Heating 17°F. D.B. ,15°F. W.B. air entering outdoor coil, 70°F. D.B. air entering indoor coil. (D) Rated indoor airflow for heating is the same as for cooling. |